Specifications
Design 10A
Fans with
Airfoil
Wheels
GENERAL:
Provide a high performance, lowmainte-
nance, centrifugal fanwith airfoil wheel and
hyperbolicwheel cone. Fan shall be licensed
to bear the AMCA Certified Ratings Seal for Air
Performance based on tests and procedures
in accordancewith AMCA standard 211. Fans
must bemanufactured and assembled in the
U.S.A. Acceptable vendors: Chicago Blower
Corporation
PERFORMANCE:
Performance shall include steep pressure and
non-overloading horsepower characteristics.
Mechanical efficiency shall be no less than
80%. Wheel inlet cone to be designed to
ensure smooth, stable air flowacross the
entire operating range. System static pressure
changes of 30% shall result in an approximate
10%volume reduction.
HOUSING:
Fan housing shall be of welded, heavy gauge
constructionwith seven common discharge
positions. Scroll is to be continuouslywelded.
ROTOR:
Wheel shall have cast iron hub (steel hub on
sizes 40-1/4, 44-1/2 and 49) lock bolted to a
heavy backplate. Airfoil blades continuously
welded to the backplate and hyperbolic
wheel cone. Wheels to be statically and
dynamically balanced toG6.3 standards in
accordancewith ISO1940 and ANSI S2.19
specifications. Shaft shall be turned, ground
and polished 1045 hot rolled steel straight-
ened to amaximumT.I.R. of .002 inches
andmounted using heavy duty ball or roller
pillowblock bearings. Shaft critical speed shall
not be less than1.25 timesmaximumRPM.
MOUNTING:
Housing and base assembly completewith
integral mounting angles for connection to
foundation. Adjustablemotor base to be
welded to base or channel.
6
FACTORYMOUNTED
MOTORS ANDDRIVES
(Accessory)
Motors and drives to be factorymounted.
Unit to be tested at running speed for vibra-
tion and balance. Filtered vibration readings,
taken at bearings, are not to exceed 0.15
inches per second.
INLET VOLUME CONTROL
(Accessory)
Inlet volume control (IVC) device shall be
totally enclosedwithin the inlet cone. IVC
device shall be 7-bladed, and pre-spin the
incoming air to control volume and pressure.
ACCESSORIES
(Choose from the following)
Slip-fit Inlet
Flanged Inlet or Outlet - PunchedHoles
Companion Flange - Punched or
Unpunched - Inlet, Outlet or Both
Type “C” AMCA Spark Resistant
Construction
1-1/2" NPT HousingDrain
Shaft Seal
Quick Clamp or Raised Bolted Access Door
Inlet Screen
Shaft CoolingWheel withGuard
(Required from300 - 800°F)
AdjustableMotor Base
Shaft and BearingGuardwith
ExtendedGrease Fittings
Totally Enclosed Belt Guard
with Ventilation Panel
Constant or Adjustable Speed
V-Belt Drives - minimum1.2 S.F.
Outlet Damper - Parallel or Opposed Blades.
Manual Operationwith LockingQuadrant.
Unitary Base: Heavy channel construction,
continuouslywelded, with fan andmotor
basewelded to insure vibration-free service.
Inlet Box: Bolt-onwith access door and
options for support legmounting and shop
assembly.